Fusebox Diagram Reference

Device abbreviations, single- and three-phase conductor colours per HD 308 S2, RCD types, RCD grouping conventions and circuit schedule columns for documenting a distribution board. Use alongside the Fusebox Diagram Generator.

Last updated: July 2026

Terms

HD 60364Harmonization Document 60364
The European adaptation of the international IEC 60364 wiring rules — most EU countries base their national electrical installation regulations on this document.
IECInternational Electrotechnical Commission
The international body that writes electrical safety standards used across most of the world outside North America. When a chart cites an IEC number, it's pointing to the official rulebook behind a calculation.
MCBMiniature Circuit Breaker
The switch in a fuse box that automatically trips (switches off) if a circuit draws too much current, protecting the wiring from overheating. It can be reset and reused, unlike a traditional fuse.
RCBOResidual Current Breaker with Overcurrent Protection
A single device that combines an MCB and an RCD — it protects a circuit both from overload/short-circuit and from earth leakage, in one unit per circuit instead of sharing one RCD across many.
RCDResidual Current Device
A safety switch that instantly cuts power if it detects electricity leaking to earth — for example through a person or a faulty appliance — protecting against electric shock.
VDEVerband der Elektrotechnik Elektronik Informationstechnik
The German electrical engineering association that publishes widely-used safety standards in Germany and beyond — similar in role to IEC, but specifically German.

Device Abbreviations

Common abbreviations used on single-line distribution board diagrams and circuit schedules.

AbbreviationDeviceTypical rating formatFunction
MainMain switch / incomere.g. 40A, 63AIsolates the whole board
RCDResidual-current devicee.g. 40A/0.03AEarth-fault (shock) protection for a group of circuits
RCBOCombined RCD + MCBe.g. B16/0.03AEarth-fault and overcurrent protection for a single circuit
MCBMiniature circuit breakere.g. B16, C32Overcurrent/short-circuit protection for one circuit
AFDDArc fault detection device (Brandschutzschalter)e.g. B16Detects dangerous arc faults — fire protection per IEC 60364-4-42 / DIN VDE 0100-420
SPDSurge protective devicee.g. Type 2Limits transient overvoltage from lightning/switching
ReserveSpare wayUnused space reserved for a future circuit

Conductor Colour Coding (HD 308 S2)

Harmonised conductor identification colours per HD 308 S2, as used across the diagram's busbar, tap wires and PE rail. Single-phase boards use L1 (brown) only; three-phase boards use all three line colours.

ConductorColourSwatch
L1 (Line 1)Brown
L2 (Line 2)Black
L3 (Line 3)Grey
N (Neutral)Blue
PE (Protective Earth)Green/Yellow stripe

Older installations (pre-harmonisation) may use different phase colours — always verify colours on-site rather than assuming from a diagram alone.

RCD Types (EN 61008 / EN 61009)

Which fault-current waveforms an RCD can detect. Informational only — the required type is a design decision for a qualified electrician.

TypeDetectsTypical use
ACSinusoidal AC fault currents onlyLegacy — should no longer be specified for new installations with electronic loads
AAC + pulsating DC fault currentsThe modern minimum for most household/commercial circuits
FType A + mixed-frequency fault currentsCircuits with frequency inverters (heat pumps, washing machines, AC units)
BType F + smooth DC fault currentsEV chargers, PV inverters, variable-frequency drives

RCD Grouping — Common Conventions

General conventions seen in practice when splitting circuits across multiple RCDs. These are background context, not a substitute for a qualified electrician's design decisions.

ConventionRationale
Separate lighting from socketsAn earth fault on a socket circuit doesn't also drop room lighting
Separate wet areas (bath/kitchen)Higher fault-risk areas isolated from the rest of the installation
Split large boards across 2+ RCDsA single nuisance trip doesn't de-energise the entire property
Dedicated RCBO for sensitive loadsIsolates one circuit (e.g. freezer, server) from unrelated trips

Circuit Schedule Columns (Stromkreisliste)

Standard columns used in the printed circuit schedule beneath the diagram.

ColumnMeaning
Nr.Auto-numbered circuit index (MCB/RCBO/AFDD rows only)
Gerät / TypProtective device type (MCB, RCBO, AFDD, RCD incl. type, SPD, Main, Reserve)
PhaseAssigned phase on three-phase boards — L1, L2, L3, or 3~ for multi-pole devices
NennstromRated current / trip curve, e.g. B16, C32
KabelCable type and cross-section, e.g. NYM-J 3×1.5
BezeichnungWhat the circuit feeds — room or load description
RCD-GruppeWhich RCD this circuit sits under, or "—" if direct from the busbar

Worked Example — Sample Schedule

A small single-phase board with two RCD groups and one direct circuit, as it would appear in the generated schedule.

Nr.Gerät / TypNennstromKabelBezeichnungRCD-Gruppe
Main switch40AMain switch
1MCBB16NYM-J 3×1.5Living room socketsRCD 1
2MCBB16NYM-J 3×1.5LightingRCD 1
3MCBB32NYM-J 3×2.5Kitchen — ovenRCD 2
4MCBB16NYM-J 3×1.5Garage (direct)

Frequently Asked Questions

Does this reference chart tell me how to design my distribution board?

No — it's background context on abbreviations, colours and common conventions used when documenting a board that has already been designed. Actual circuit design, protection coordination, RCD/AFDD requirements and RCD grouping decisions must be made by a qualified electrician (Elektrofachkraft) per the applicable national standard based on IEC 60364 / HD 60364 (e.g. DIN VDE 0100 in Germany).

Why does the schedule leave the Nr. column blank for some rows?

Only MCB, RCBO and AFDD rows feed a load directly, so only they get an auto-incrementing circuit number. Main, RCD, SPD and reserve rows organise or protect the board itself rather than feeding an individual circuit.

Aren't black and grey conductors a sign of old wiring?

Not on three-phase installations — under HD 308 S2, black and grey are the current standard colours for L2 and L3, alongside brown for L1. On old single-phase wiring, however, black or grey line conductors can indicate pre-harmonisation colours — always verify actual conductor colours on-site rather than relying on a diagram alone.